The Juice Goose SRA 07500 Rackmount Line Interactive UPS incorporates automatic voltage regulation (line interactive) function that preserves battery power and supports sensitive electronic equipment during brown outs. Once incoming voltage drops below operational levels, SRA switches to battery to maintain power continuity. These products also provide 960 Joules of power line surge protection.
Line Interactive circuitry monitors the incoming voltage level and routes current through the appropriate taps on a buck/boost transformer to raise or lower output voltage, improving the performance of powered equipment and extending the usable range of the utility power before switching to battery mode.
Juice Goose SRA 07500 Features
- Voltage regulation
- Emergency Power Off
- Hot swappable battery design
- Easy to view LCD panel
- Maintenance free batteries
- SRA 07500 750VA/525W rackmount line interactive UPS1
- Rating VA750
- Capacity Watts525
- Input
- Rated Operating Voltage (VAC): 120 = Nominal, 90 to 150 = Min and Max Range
- Low Voltage Transfer to Battery: 89 VAC
- Return to Utility Power: 94 VAC
- High Voltage Transfer to Battery: 151 VAC
- Return to Utility Power: 146 VAC
- Power Cord: 10 Foot, NEMA 5-15P (NEMA 5-20P for SRA 20000)
- Output
- Output Voltage
- Line Interactive Mode: 103 - 136 VAC
- Battery Mode: 120 VAC +/- 5%
- Frequency Range: 60 Hz +/- 0.8%
- Overload Capacity: 110% 20 - 60 Seconds, 150% Immediate Shutdown
- Harmonic Distortion (THDU): 30.3 % to 37.2 % = Total, 14.5 % to 18.7 % = Single
- Transfer Time AC to DC: 6-10ms (typical)
- Topology (design): Line Interactive - Simulated Sine Wave
- Receptacles: 8 x NEMA 5-15R
- Load Shedding (outlet control) requires third-party software: 2 Banks of 3 Outlets and 2 Unswitched. SRA 20000 has 1 Unswitched L5-20R
- Battery
- Battery Type: Sealed, Non-Spillable, Valve Regulated, Maintenance Free, Lead Acid
- Run Time (full load/ half load): 4 minutes / 14 minutes
- Typical Recharge Time: 8 hours to 90% from full discharge
- Typical Service Life: 3 to 5 years with proper operation
- Surge Protection
- Surge Energy Rating: 960 joules
- Surge Capacity: 6,500 amps total (one time)
- EMI/RFI Noise Filtration: >45dB normal and common mode
- Display, Control, and Alarms
- Status Indications: Battery Capacity, Load Percentage, Input Power Source, External Power Line, Fault Indications
- Control Select Buttons: On/Off/Test, Alarm Silence, Display Control (Scroll)
- Warning Indicators: Low or Bad Battery, Current Overload, Site Wiring Fault, Over Temperature, UPS Failure
- Audible Noise Output @ 3 ft< 45 dBA
- Humidity20 to 90% RH (non-condensing)
- Operating Temperature32°F to 104°F (0°C to 40°C)
- Storage Temperature-13°F to 104°F (-25°C to 40°C)
- Weight31.3 pounds
- Dimensions (LxWxH)16.1" x 18.9" x 3.4"